제습 증발냉각 기반 전 외기 공조시스템의 환기 성능 평가Ventilation performance evaluation of liquid desiccant in an evaporative-cooling assisted 100% outdoor air system
- Other Titles
- Ventilation performance evaluation of liquid desiccant in an evaporative-cooling assisted 100% outdoor air system
- Authors
- 윤동섭; 이성준; 박준영; 정재원
- Issue Date
- Oct-2015
- Publisher
- 대한건축학회
- Keywords
- 환기; 추적기체법; 전 외기 공조시스템; 시간 당 환기 횟수; Ventilation; tracer gas technique; 100% outdoor air system; air change rate
- Citation
- 대한건축학회 창립70주년기념대회 및 추계학술발표대회논문집, v.35, no.2, pp.281 - 282
- Indexed
- OTHER
- Journal Title
- 대한건축학회 창립70주년기념대회 및 추계학술발표대회논문집
- Volume
- 35
- Number
- 2
- Start Page
- 281
- End Page
- 282
- URI
- https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/156055
- ISSN
- 2287-5786
- Abstract
- In this study, ventilation performance of liquid desiccant in an evaporative-cooling assisted 100% outdoor air system was evaluated. Carbon-dioxide gas was used as a tracer gas to evaluate the ventilation performance. Air change rate (ACR) was considered as a ventilation efficiency index. CO₂ gas was injected in to test room of 81 m³ and concentration decay was measured when ventilating room with LD-IDECOAS and VAV system. Supply air flow rate of two system is set to 1500 CMH and 1200 CMH of return air was used in VAV system. Conquently, it was found that the LD-IDECOAS has better ventilation performance than VAV system.