Energy saving potential of various air-side economizers in a modular data center

Authors
Ham, Sang-WooKim, Min-HwiChoi, Byung-NamJeong, Jae-Weon
Issue Date
Jan-2015
Publisher
ELSEVIER SCI LTD
Keywords
Modular data center; Cooling system; Air-side economizer; Evaporative cooling; Energy savings
Citation
APPLIED ENERGY, v.138, pp.258 - 275
Indexed
SCIE
SCOPUS
Journal Title
APPLIED ENERGY
Volume
138
Start Page
258
End Page
275
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/158177
DOI
10.1016/j.apenergy.2014.10.066
ISSN
0306-2619
Abstract
With the recent development of the IT technology, the demand for data centers has significantly increased, and modular data centers have attracted considerable attention because of their excellent stability, scalability, and economic feasibility. This research quantitatively analyzed the applicability of various air-side economizers and their energy-saving potential in modular data centers. A detailed cooling load estimation process was established for modular data centers, and annual cooling energy simulations were carried out using various air-side economizers. The various air-side economizers yielded cooling coil load savings of 76-99% in comparison to conventional cooling systems in data centers, and the total cooling energy savings of the economizers ranged from 47.5% to 67.2%. Indirect air-side economizers with high-effectiveness heat exchangers were found to yield significant energy saving (63.6%) and have simple system configurations.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE