컨테인먼트가 적용된 모듈러 데이터센터의 공조 팬 제어 방안에 관한 실험적 연구An experimental study on the fan control of computer room air handler in a modular data center with cold-aisle containment

Other Titles
An experimental study on the fan control of computer room air handler in a modular data center with cold-aisle containment
Authors
함상우김민휘윤동섭정재원
Issue Date
Oct-2014
Publisher
대한건축학회
Keywords
모듈러 데이터센터; 공조 팬 제어; 컨테인먼트; Modular Data Center; CRAH Fan Control; Containment
Citation
대한건축학회 추계학술발표대회논문집, v.34, no.2, pp.285 - 286
Indexed
OTHER
Journal Title
대한건축학회 추계학술발표대회논문집
Volume
34
Number
2
Start Page
285
End Page
286
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/158805
ISSN
2287-5786
Abstract
The purpose of this study is to experimentally demonstrate the fan control strategy of computer room air handler (CRAH) in amodular data center with containment architecture. In containment architecture, variable speed drive fan is widely accepted in orderto reduce fan energy. However, the selection of inappropriate control variable for fan speed yields improper operation of fan; fanairflow does not change when the IT equipment is in part-load operation. In this study, fan control strategy that modulates fanspeed according to the differential pressure between cold- and hot-aisle through containment is experimented. As a result, thisstrategy reduces the discrepancy between rack and CRAH fan airflow though small recirculation is occurred due to gap betweenfloor and racks.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE