Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

공조기를 이용한 가압테스트를 통한 외피 기밀도 실측Building Envelope leakage measurement using the air-handler fan pressurization approach

Other Titles
Building Envelope leakage measurement using the air-handler fan pressurization approach
Authors
한슬기조홍재정재원
Issue Date
Oct-2012
Publisher
한국건축친환경설비학회
Keywords
공조기를 이용한 가압테스트; 건물 기밀도; 팬 가압 테스트; 건물 침기량; AHU pressurization test; Air-tightness; Air leakage test; Buildling Envelope
Citation
한국건축친환경설비학회 2012년도 추계학술발표대회, pp.109 - 112
Indexed
OTHER
Journal Title
한국건축친환경설비학회 2012년도 추계학술발표대회
Start Page
109
End Page
112
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/164440
Abstract
This research is a case study performing the air-andler fan pressurization test in a real building. The test has been performed follwing an exiting test method(i.e. CGSB 149.15-96 Standrard). The test building is a 5-story office with a square (32.4m × 32.4m) footprint built in 2001 at Dae-jeon. The test building gas four air-handling units, but the unit located at the basement was out of order. Consequently, the 3 air-handling units installed at the 1st floor and 5th floor were used to pressurize the building. To measure the whole building envelope air leakage, the SA airflow rates in each air handler, operated at the 100% outdoor air mode with closed return and exhaust air dampers, were monitored together with the building pressure. This paper provides some practical information acquired in the field measurement of envelope leakage using the established air-handler fan pressurization test method.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE