다수의 냉각탑이 설치된 옥상에서 냉각탑별 재유입률 예측Prediction of Reentering Ratio of Individual Cooling Towers Scatteredon a Building Roof

Other Titles
Prediction of Reentering Ratio of Individual Cooling Towers Scatteredon a Building Roof
Authors
이태구문선애유호선이재헌
Issue Date
Nov-2006
Publisher
대한설비공학회
Keywords
Cooling tower(냉각탑); Recirculation(재순환); Interference(간섭); Reentering rate(재유입률)
Citation
설비공학 논문집, v.18, no.11, pp.923 - 932
Journal Title
설비공학 논문집
Volume
18
Number
11
Start Page
923
End Page
932
URI
http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/19055
ISSN
1229-6422
Abstract
In this paper, reentering ratio and cooling capacity of individual cooling towers arrayed on a building roof were studied by a numerical method. The number of 16 cooling towers were divided into 4 banks. It was considered the summer prevailing wind characteristics as west wind and south wind of 5m/s. It was also considered the roofwall types as the curtainwall and the louverwall that had the outdoor air intake louver in the curtainwall. In this case, the louver was suggested as the solution that could prevent reentering phenomenon due to recirculation and interference of the discharge air. In the case of the curtainwall, the averaged reentering ratio are predicted 13.3% and 24.4% for the west and south wind of 5 m/s, respectively. In the case of the louverwall, the averaged reentering ratio are predicted 2.5% and 9.7% for the west and south wind of 5m/s, respectively. Therefore, the louverwall is a appropriate solution for reducing the reentering phenomenon.
Files in This Item
Go to Link
Appears in
Collections
College of Engineering > ETC > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Yoo, Ho seon photo

Yoo, Ho seon
College of Engineering (School of Mechanical Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE