냉각탑 주위의 장애물에 의한 재순환 현상에 관한 수치해석Numerical Analysis on Recirculation Generated by Obstacles around a Cooling Tower
- Authors
- 이정희; 최영기
- Issue Date
- 2006
- Publisher
- 대한설비공학회
- Keywords
- Recirculation; Obstacle; Cooling tower; Air-guide; 재순환; 장애물; 냉각탑; 에어가이드
- Citation
- 설비공학 논문집, v.18, no.7, pp 578 - 586
- Pages
- 9
- Journal Title
- 설비공학 논문집
- Volume
- 18
- Number
- 7
- Start Page
- 578
- End Page
- 586
- URI
- https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/29017
- ISSN
- 1229-6422
- Abstract
- The present study has been conducted to examine the effect of obstacles around a cooling tower and an air-guide to prevent recirculation. In order to analyze the interaction between external flow and cooling tower exit flow, the external region as well as the coolingtower are included in computational domain. Two dimensional analysis is performed using the finite volume method with non-orthogonal and unstructured grid system. The standard turbulence model is used. To investigate the recirculation phenomena, flow and temperature fields are calculated with three approaches such as, the distance between cooling tower and obstacle, the allocated geometrical type, and the effect of height of obstacle. In addition, the air-guide is considered in the current computation. The mean recirculation rate increases with the height of obstacle. The effect of air-guide to reduce the mean recirculation rate is obviously observed.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > School of Mechanical Engineering > 1. Journal Articles
![qrcode](https://api.qrserver.com/v1/create-qr-code/?size=55x55&data=https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/29017)
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.