Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

워터미스트 작동에 의한 산소저공급 실내화재 특성 변화에 대한 수치해석 연구Numerical study on the change in fire characteristic as operating water-mist in under-ventilated compartments

Authors
고권현이성혁유홍선
Issue Date
2008
Publisher
한국액체미립화학회
Keywords
Compartment fires; Heat release rate; under-ventilated fires; water-mist; 공간 화재; 발열량; 산소저공급 화재; 워터미스트
Citation
한국액체미립화 학회지, v.13, no.3, pp 156 - 161
Pages
6
Journal Title
한국액체미립화 학회지
Volume
13
Number
3
Start Page
156
End Page
161
URI
https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/36366
ISSN
1226-2277
Abstract
The present article reports a numerical study on the fire characteristic change by water-mist in under-ventilated compartments. The natural gas and heptane pool fires are used as fire sources, which are located in the bottom center of the 2/5 reduced-scaled model of the ISO 9705 standard room. The fire modeling using the FDS (Fire Dynamics Simulator) is validated by comparison with previously published experimental results. For temperature and combustion gas concentrations at two positions located in the upper layer of compartment, the predicted results with and without water-mist are compared each other. The results show that under the water-mist operation, the predicted temperature and carbon monoxide concentration reduce as 300 ~ 400 °C and about 20%, respectively, compared to those without water-mist.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > School of Mechanical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Seong Hyuk photo

Lee, Seong Hyuk
공과대학 (기계공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE