Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Assessment of appropriate SFCL type considering DC fault interruption in full bridge modular multilevel converter HVDC system

Authors
Lee, Ho-YunAsif, MansoorPark, Kyu-HoonLee, Bang-Wook
Issue Date
Aug-2019
Publisher
Elsevier BV
Keywords
Full bridge (FB); High-voltage direct-current (HVDC); Modular multilevel converter (MMC); Resistive type SFCL (R-SFCL); Saturated iron core type SFCL (SIC-SFCL)
Citation
Physica C: Superconductivity and its Applications, v.563, pp 1 - 6
Pages
6
Indexed
SCI
SCIE
SCOPUS
Journal Title
Physica C: Superconductivity and its Applications
Volume
563
Start Page
1
End Page
6
URI
https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/2376
DOI
10.1016/j.physc.2019.04.006
ISSN
0921-4534
1873-2143
Abstract
The modular multilevel converter (MMC) is the most promising converter topology for implementations of voltage source converter (VSC) high-voltage direct-current (HVDC) grid. Existing research has focused on operational characteristics and improvement of efficiency by optimizing the control. Among various MMC topologies, a full bridge (FB) sub-module (SM) MMC with fault interruption capability has attracted attention because it does not require a dc circuit breaker. However, the most severe faults on dc line, can cause steeply rising fault currents with high peak magnitude, but there is a lack of literature regarding fault current reduction in FB-MMC systems. This problem can be overcome by applying the fault current limiter (FCL) and the superconducting fault current limiters (SFCLs), which have already been developed for the ac grid, have been considered in this paper. We have verified the applicability of two well-known SFCL types i.e., resistive SFCL (R-SFCL) and saturated iron core type SFCL (SIC-SFCL) in FB-MMC grid. Current limiting characteristics and energy dissipation has been according to the location of fault on dc line has been studied. We compared the merits and demerits of the aforementioned SFCLs based on the simulation results. The results indicate, SIC-SFCL to be the most suitable fault current limiter for FB-MMC HVDC system application. (C) 2001 Elsevier Science. All rights reserved
Files in This Item
Go to Link
Appears in
Collections
COLLEGE OF ENGINEERING SCIENCES > SCHOOL OF ELECTRICAL ENGINEERING > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Bang Wook photo

Lee, Bang Wook
ERICA 공학대학 (SCHOOL OF ELECTRICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE