Evaluation of the Reliability of Insulating Gases for the Bushing in Cryogenic Environment

Authors
Shin, Woo-JuHwang, Jae-SangSeong, Jae-KyuSeo, In-JinKim, Yong-HanLee, Bang-Wook
Issue Date
Jun-2013
Publisher
Institute of Electrical and Electronics Engineers
Keywords
Cryogenic bushing; high voltage; liquid nitrogen; long-term breakdown; superconducting equipment
Citation
IEEE Transactions on Applied Superconductivity, v.23, no.3
Indexed
SCIE
SCOPUS
Journal Title
IEEE Transactions on Applied Superconductivity
Volume
23
Number
3
URI
https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/27641
DOI
10.1109/TASC.2013.2241814
ISSN
1051-8223
Abstract
Conventional high-voltage bushings, which adopt SF6 gas as an insulation media, cannot be directly applied in cryogenic environment due to the liquefaction of SF6 gas. In our previous study, it was shown that SF6 gas could not be used as an insulation gas in cryogenic environment, but instead, CF4 gas has shown excellent insulation properties with little liquefaction phenomena, and have a possibility to be applied for the insulation gas for high-voltage bushings in cryogenic environment. However, in order to apply CF4 gas for cryogenic bushing, it should be determined whether CF4 gas can maintain its insulation characteristics in long-term operation. In order to reveal the long-term insulation properties of various gases, which have a possibility to be applied in high-voltage bushings in cryogenic environment, the long-term breakdown characteristics of CF4 gas, SF6 gas, N-2 gas, and dry-air were compared over time in a cryogenic environment. For an experiment, a high-vacuum cryostat and a cryo-cooler were prepared to prevent the evaporation of liquid nitrogen for long-term duration. An fiberglass reinforced plastics bushing was installed on the cryostat to apply high voltage up to 60 kV. A rod to plane electrode was set in a cryostat to determine the breakdown voltage of insulating gases. The lightning impulse and ac overvoltage tests have been performed and the test results were analyzed. From the test, the reduction of breakdown voltage of CF4 gas were observed as time passed by, and it was more severe in SF6. However, stable breakdown characteristic have been shown with N-2 gas. Therefore, increasing the pressure of N-2 would be a viable option for increasing the breakdown voltage in a cryogenic environment.
Files in This Item
Go to Link
Appears in
Collections
COLLEGE OF ENGINEERING SCIENCES > SCHOOL OF ELECTRICAL ENGINEERING > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Bang Wook photo

Lee, Bang Wook
ERICA 공학대학 (SCHOOL OF ELECTRICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE