Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Short-Term and Long-Term Dielectric Characteristics of Molded Compound According to Various Portion of Alumina Trihydrate Micro-Filler

Authors
Hwang, RyulNa, Jin yongKoo, Jae hongKang, Jong sungLee, Bang wook
Issue Date
Sep-2018
Publisher
Institute of Electrical and Electronics Engineers Inc.
Keywords
ATH; BMC; Breakdown; Long-Term; Short-Term; VCB
Citation
2018 Condition Monitoring and Diagnosis, CMD 2018 - Proceedings
Indexed
OTHER
Journal Title
2018 Condition Monitoring and Diagnosis, CMD 2018 - Proceedings
URI
https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/7970
DOI
10.1109/CMD.2018.8535834
ISSN
0000-0000
Abstract
The demand on electric power is expected to increase continuously due to the development of industry and the congestion of cities which requires large capacity and high voltage transmission for electric power system. In addition, electric power of good quality, compacted electric power device, reliable and secure electric system are also required. For these reasons, solid insulation materials are preferred due to its advantage on size reduction and weight lightening. Solid dielectric materials improve the electric breakdown strength by suppresses the initiation and propagation of breakdown. However, the characteristics of solid dielectric materials are apt to influenced by operation voltage, period of use and the condition of internal solid insulation material. Especially, the internal deterioration of solid dielectric due to the increment of operation period in rated voltage condition could cause breakdown of the electric power apparatuses. In this paper, short term and long-term breakdown tests for Bulk Molded Compound (BMC) with various portion of Alumina Trihydrate (ATH) micro filler were carried out to find out the dielectric performance of solid dielectric introduced in Vacuum Circuit Breaker (VCB) product. The long-term breakdown test corresponds to consideration of the operation voltage of VCB to establish the lifetime and insulation reliability of dielectric material. The short-term breakdown tests were conducted in mineral oil with sphere - sphere electrodes for BMC with 0, 25, 40% of ATH. The long-term breakdown test was carried out for the voltage level of 3, 5, 10% of one - minute step - up tests based on the results from the short test breakdown test and the comparison analysis on the time to breakdown has been performed. From the test results, the breakdown voltage of BMC with 25% of ATH specimen was increased compared to specimen with 0% one, and the breakdown voltage of BMC with 40% ATH specimen was slightly higher than 25% one. In case of long term breakdown test, the time to breakdown was reduced in case of BMC with 40% ATH compared to 25% one. © 2018 IEEE.
Files in This Item
Go to Link
Appears in
Collections
COLLEGE OF ENGINEERING SCIENCES > SCHOOL OF ELECTRICAL ENGINEERING > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Bang Wook photo

Lee, Bang Wook
ERICA 공학대학 (SCHOOL OF ELECTRICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE