Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Influence on Configuration of Contact Support with Slits for Axial Magnetic Field Vacuum Interrupter

Authors
Na, Jin yongCha, Young kwangKoo, Jae hongShin, Tea yongSeo, Cheong wonLee, Bang wook
Issue Date
Sep-2018
Publisher
Institute of Electrical and Electronics Engineers Inc.
Keywords
AMF vacuum interrupter; angle of slits; contact support configuration; number of slits
Citation
Proceedings - International Symposium on Discharges and Electrical Insulation in Vacuum, ISDEIV, v.2, pp.659 - 662
Indexed
OTHER
Journal Title
Proceedings - International Symposium on Discharges and Electrical Insulation in Vacuum, ISDEIV
Volume
2
Start Page
659
End Page
662
URI
https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/7972
DOI
10.1109/DEIV.2018.8537034
ISSN
1093-2941
Abstract
The axial magnetic field (AMF) vacuum interrupter (VI) with excellent current breaking performance even at long stroke require the contact support made of stainless steel (SUS) unlike other type of VI. The contact support prevents AMF contact from the high impact caused by closing operation of VI with long stroke. In our previous research, it was confirmed that the current breaking performance of AMF VI was influenced by the configuration of contact support. Accordingly, it is important to determine the configuration of contact support to develop VI with high voltage performance and large current breaking capacity. In this paper, the effect of number of slits and angle of slits in contact support was investigated on the current breaking performance of AMF VI. The current breaking performances i.e., maximum axial magnetic flux density at current peak (B z ), effective area (/boldsymbol/lambda), maximum axial magnetic flux density at current zero (B zo ) were derived by three-dimensional finite element method (3D-FEM). From the simulation results, it was confirmed that number of slits somewhat affects the current breaking performance although the influence was insignificant in case of more than four slits. On the other hand, angle of slits has no influence on the current breaking performance. © 2018 IEEE.
Files in This Item
Go to Link
Appears in
Collections
COLLEGE OF ENGINEERING SCIENCES > SCHOOL OF ELECTRICAL ENGINEERING > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Bang Wook photo

Lee, Bang Wook
ERICA 공학대학 (SCHOOL OF ELECTRICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE