Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Comparison of Surface Flashover Characteristics of Rod and Rib Type Post Insulator for Extra-High Voltage Superconducting Fault Current Limiter

Authors
Koo, Jae-HongShin, Woo-JuOh, Dong-HunHwang, RyulLee, Bang-Wook
Issue Date
Jun-2017
Publisher
Institute of Electrical and Electronics Engineers
Keywords
Electric field analysis; glass fiber reinforced polymer (GFRP); liquid nitrogen (LN2); ribbed post insulator; rod post insulator; superconducting fault current limiter (SFCL); surface flashover
Citation
IEEE Transactions on Applied Superconductivity, v.27, no.4
Indexed
SCI
SCIE
SCOPUS
Journal Title
IEEE Transactions on Applied Superconductivity
Volume
27
Number
4
URI
https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/9564
DOI
10.1109/TASC.2017.2667892
ISSN
1051-8223
1558-2515
Abstract
One of the most important insulating components for developing a 154 kV superconducting fault current limiter (SFCL) is post insulator, which supports 154-kV SFCL modules in a cryostat. In order to design an optimum post insulator, the top priority is to determine the creepage distance of post insulator. In our previous research, surface flashover voltages along smooth glass fiber reinforced polymer (GFRP) rods immersed in liquid nitrogen (LN2) were experimentally investigated. To reduce the cryostat volume, ribbed post insulators with increased creepage path were then considered. However, due to difficulties with producing ribbed GFRP post insulators, ribbed specimens weremade of polytetrafluoroethylene instead. Four kinds of test specimens were prepared to determine the position and the number of ribs attached to the surface. From the experimental results, it was found that the ribbed insulator has shown better insulation performance in LN2 and number of ribs could affect the surface flashover voltage of post insulator. Consequently, ribbed model for 154-kV SFCL post insulator was designed and successfully tested. Finally, real 154-kV SFCL system with newly designed ribbed post insulator was installed and Basic Impulse Level (BIL) test and ac required withstand voltage were successfully carried out.
Files in This Item
Go to Link
Appears in
Collections
COLLEGE OF ENGINEERING SCIENCES > SCHOOL OF ELECTRICAL ENGINEERING > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Bang Wook photo

Lee, Bang Wook
ERICA 공학대학 (SCHOOL OF ELECTRICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE